Weil-McLain Boiler: Check air pressure switch setting with manometer

Updated · by Aurora Star Tech Inc.

Check air pressure switch setting with manometer on a Weil-McLain boiler: Confirm the air pressure switch closes at the correct draft reading during ignition attempts.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: CGi-25 to CGi-8

Common causes of check air pressure switch setting with manometer

  • Blocked or kinked hoses
  • Blockage in the inducer outlet or block assembly
  • Loose inducer wheel or wrong inducer rpm
  • Inducer back plate not sealed

How to fix check air pressure switch setting with manometer: step by step

  1. Keep boiler water at 100 F or cooler before starting so readings are valid.
  2. Confirm the red hose goes from the black (+) barb to the right side collector hood tapping, and the white hose goes from the tan (-) barb to the left side tapping between flue collector and inducer. On CGi-7 and -8 the red hose goes to the Y-fitting on both (+) barbs.
  3. Remove the air pressure switch hoses from the switch (or Y-fitting on dual switches).
  4. Install tees and tubing to the inclined manometer.
  5. Turn off gas and call for heat. The inducer runs but burners do not light.
  6. Check for 24 VAC between both air pressure switch terminals.
  7. If the manometer reads below the switch setpoint, check hoses, inducer outlet, inducer wheel, rpm, back plate seal and block assembly.
  8. If the manometer reads above setpoint but there is no 24 VAC across the switch terminals, replace the air pressure switch.
  9. When correct, remove the tees and reinstall the hoses.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: CGi Series 5 boiler manual, p. 75. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.