Weil-McLain Boiler: Category II (negative pressure) vent requirements
Category II (negative pressure) vent requirements on a Weil-McLain boiler: SlimFit boilers can be installed as Category II with a designed vent system. The vent must hold negative pressure, and flue temperature must stay under the shutdown limit.
Applies to: SlimFit SF1000, SF1500, SF2000 in Category II configuration
Common causes of category ii (negative pressure) vent requirements
- Positive pressure in the vent causing flue gas spillage and carbon monoxide
- Flue gas over 216 F causing the boiler to shut down and recycle
How to fix category ii (negative pressure) vent requirements: step by step
- Use a professionally designed and engineered vent system per the local authority having jurisdiction.
- Use vertical vent only and do not install into an existing common vent.
- Take combustion air from the boiler room and follow the direct exhaust opening rules.
- Use a 10 in SlimFit Vent/Air adapter for the Category II vent connection.
- Install a 3 ft straight run of 10 in pipe directly after the adapter before any change in diameter or direction.
- Check that the vent pressure just after the boiler stays within the Table 1 negative pressure range at all firing rates.
- Keep flue gas under 216 F. Typically flue gas runs within 20 F of return water temperature; use the lowest expected return temperature for calculations.
- Install a carbon monoxide detector in the boiler room and wire it to the same circuit as the boiler.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit 1000-2000 Series 2 boiler manual, p. 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.