Weil-McLain Boiler: Category II draft control devices
Category II draft control devices on a Weil-McLain boiler: Because the SlimFit runs cooler flue gas, it may not create enough draft. Add draft control and safety devices as recommended to keep negative pressure in range.
Applies to: Category II vent systems
Common causes of category ii draft control devices
- Lower flue gas temperature giving less natural draft
- Chimney fan or power venter running outside the negative pressure range
- Exhaust gas leaking back into the boiler room
How to fix category ii draft control devices: step by step
- Consider a variable speed chimney fan or power venter to hold the correct negative pressure.
- Wire a flow proving switch into the boiler LCI circuit.
- Consider a double acting barometric damper or modulating damper to hold negative pressure.
- When any damper is used, install a thermal spill switch to detect exhaust entering the boiler room.
- Check that the thermal spill switch temperature range suits the SlimFit flue gas temperature.
- Set the spill switch point per the system designer and local authority having jurisdiction.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit 1000-2000 Series 2 boiler manual, p. 28. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.