Weil-McLain Boiler: Boiler room combustion air openings
Boiler room combustion air openings on a Weil-McLain boiler: Direct exhaust boilers take combustion and ventilation air from the boiler room. Openings must be sized for all appliances and air movers in the room. If the room is tight construction, provide outside air openings. Openings must not be under negative pressure from exhaust fans. Free area is after louver or grille reduction. Use the sizing rules in the manual.
Applies to: Direct exhaust installations
Common causes of boiler room combustion air openings
- Negative pressure from exhaust fans or other ventilation devices
- Louvers or grilles reducing free area
- Tight building construction
How to fix boiler room combustion air openings: step by step
- Calculate total appliance input in Btuh for the room.
- Size openings using the manual's rule for the number of appliances in the room (two openings or a single opening).
- Subtract louver or grille blockage from the free area.
- Check that the room is not under negative pressure.
- For a single opening, make sure it opens directly to outdoors, its top is within 12 in of the ceiling, and its free area is at least the sum of all vent connector areas in the space.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit series 3 commercial gas-fired water boiler manual, p. 26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.