Weil-McLain Boiler: Boiler does not start
Boiler does not start on a Weil-McLain boiler: Checklist from the start-up section when the boiler fails to light.
Applies to: CGi-25 to CGi-8
Common causes of boiler does not start
- Loose connection, blown fuse or service switch off
- Boiler temperature setting below boiler water temperature
- Thermostat set below room temperature
- Gas not turned on at the meter or boiler
- Incoming gas pressure too low (below 5 in. w.c. natural gas, or below 11 in. w.c. propane)
How to fix boiler does not start: step by step
- Check for loose connections, a blown fuse or the service switch being off.
- Confirm the boiler temperature setting is above the boiler water temperature.
- Confirm the thermostat is set above room temperature.
- Confirm gas is on at the meter and at the boiler.
- Check incoming gas pressure: at least 5 in. w.c. for natural gas or 11 in. w.c. for propane.
- If none of these fixes the problem, go to the troubleshooting section.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: CGi Series 5 boiler manual, p. 64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.