Weil-McLain Boiler: Automatic air vent check

Updated · by Aurora Star Tech Inc.

Automatic air vent check on a Weil-McLain boiler: Applies only to systems with diaphragm-type expansion tanks. Automatic air vents must not be used with other tank types.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: 110/155/220/299/300/399 Series 2 with diaphragm expansion tank

Common causes of automatic air vent check

  • Air vent stuck or leaking

How to fix automatic air vent check: step by step

  1. Remove the cap from the automatic air vent.
  2. Depress the valve pin slightly with a screwdriver tip and check that the vent operates freely without leaking. Water from the vent may be very hot.
  3. Reinstall cap A, twisting it all the way on.
  4. Loosen cap A one turn so the vent can operate.
  5. Have the vent replaced if it does not operate correctly.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Evergreen Series 2 user's information manual, p. 8. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.