Weil-McLain Boiler: ASME high temperature limit installation
ASME high temperature limit installation on a Weil-McLain boiler: If the install must meet ASME requirements, an external high limit is needed. Set it at least 20°F above the operating setpoint. The external limit can be set to a maximum of 240°F, and the boiler operating limit is 210°F.
Applies to: CGi-25 to CGi-8
How to fix asme high temperature limit installation: step by step
- Install the high limit control in the supply piping between the boiler and its isolation valve.
- Set the external high limit at least 20°F above the operating setpoint.
- Do not set the external high limit above 240°F.
- Confirm the boiler operating limit is 210°F.
- Wire the control as shown on page 46.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: CGi Series 5 boiler manual, p. 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.