Weil-McLain Boiler: Application B3 piping and circulator requirements
Application B3 piping and circulator requirements on a Weil-McLain boiler: Multi-zone space heating with boiler-only DHW, used with the Ultra easy-up manifold. Piping must be primary/secondary. The boiler must sit downstream of the heat pump when they run together, so high return temperatures do not shut the heat pump down. A mixing valve limits DHW temperature. Zone circulators are sized for required flow by the installer. The boiler circulator ships loose with the boiler. The heat pump circulator is in the heat pump manifold.
Applies to: Application B3 (Ultra easy-up manifold)
Common causes of application b3 piping and circulator requirements
- High return temperature to the heat pump if the boiler is upstream of it
How to fix application b3 piping and circulator requirements: step by step
- Pipe the system primary/secondary.
- Place the boiler downstream of the ECO HP.
- Install a mixing valve to limit supplied DHW temperature.
- Size the zone circulators for the required flow.
- Install the boiler circulator (shipped loose with the boiler).
- Confirm the heat pump circulator is in the heat pump manifold.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO HP Heat Pump Application Guide, p. 36. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.