Weil-McLain Boiler: Annual startup: inspect ignition electrode
Annual startup: inspect ignition electrode on a Weil-McLain boiler: The ignition electrode is the longer rod with a brown ceramic insulator. It mounts on the burner end section.
Applies to: SlimFit 1000-2000 MBH Series 2
Common causes of annual startup: inspect ignition electrode
- White oxide buildup on the electrode
- Worn or damaged gasket
- Ground wire loose
How to fix annual startup: inspect ignition electrode: step by step
- Remove the ignition electrode from the burner end section of the heat exchanger.
- Remove white oxides with steel wool. If it cannot be cleaned well, replace the ignitor.
- Reinstall the electrode with the gasket in good condition and correctly positioned. Replace the gasket if needed.
- Make sure the ignitor ground wire is under the top screw that holds the ignitor to the casting.
- Ignition electrode must be on the burner end. Flame sensor must be on the piping end. Wrong placement can cause poor ignition and lockout.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 89. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.