Weil-McLain Boiler: Annual startup: check water system and cold fill pressure
Annual startup: check water system and cold fill pressure on a Weil-McLain boiler: Check that the water system is correct and that pressure stays within limits while the boiler heats.
Applies to: SlimFit 1000-2000 MBH Series 2
Common causes of annual startup: check water system and cold fill pressure
- Expansion tank undersized or not performing
- Air trapped in system
- Incorrect cold fill pressure
How to fix annual startup: check water system and cold fill pressure: step by step
- Confirm all system components are installed correctly and working.
- Check cold fill pressure. It should be about 12 psig.
- Watch system pressure while the boiler heats. Excess rise points to expansion tank sizing or performance.
- Remove air vent caps and briefly press the push valve to flush each automatic air vent. Reinstall the caps.
- Check that vents do not leak and replace any that do.
- Check system water chemistry (inhibitor concentration, pH and hardness). See page 79 of the manual.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 89. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.