Weil-McLain Boiler: Annual startup: check expansion tank
Annual startup: check expansion tank on a Weil-McLain boiler: Confirm the expansion tank type is correct, its fill level or charge is right, and it is sized for the system.
Applies to: SlimFit 1000-2000 MBH Series 2
Common causes of annual startup: check expansion tank
- Closed-type tank waterlogged
- Diaphragm or bladder tank too small or membrane damaged
- Frequent relief valve weeping
How to fix annual startup: check expansion tank: step by step
- If the relief valve weeps often, suspect a waterlogged or undersized tank.
- Closed-type tank: install a tank fitting if none is present. Check fill level per the fitting manufacturer. If level is correct, check tank size. Replace with a larger tank if needed.
- Diaphragm or bladder tank: check that the tank is large enough. Add tanks if undersized.
- Diaphragm or bladder tank: if size is correct, remove it and check charge pressure (usually 12 psig for residential). If it will not hold pressure, replace the tank.
- Do not use automatic air vents on systems with closed-type tanks.
- Systems with diaphragm or bladder tanks need at least one automatic air vent, preferably on top of an air eliminator.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 89. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.