Weil-McLain Boiler: Annual startup: check boiler relief valve
Annual startup: check boiler relief valve on a Weil-McLain boiler: Operate the relief valve lever to confirm the waterway is clear. Relief valve reinspection is also required on a set schedule.
Applies to: SlimFit 1000-2000 MBH Series 2
Common causes of annual startup: check boiler relief valve
- Mineral deposits blocking the valve
- Valve weeping or not seating
- System overpressure from a waterlogged or undersized expansion tank
How to fix annual startup: check boiler relief valve: step by step
- Before lifting the lever, confirm a discharge line is piped to a safe disposal point.
- Lift the lever and confirm water flows.
- If the valve weeps or will not seat, replace it.
- Before replacing, confirm the weeping is from the valve and not from system overpressure due to expansion tank waterlogging or undersizing.
- If no water flows when the lever is lifted, the valve is inoperative. Shut the boiler down until a new relief valve is installed.
- Operate the lever at least once a year.
- Have a licensed plumbing contractor or authorized inspection agency reinspect the relief valve at least every three years.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 89. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.