Weil-McLain Boiler: Annual startup and maintenance schedule

Updated · by Aurora Star Tech Inc.

Annual startup and maintenance schedule on a Weil-McLain boiler: Service technician tasks for the annual startup, plus owner tasks that run daily, monthly, every six months and at end of season.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SlimFit Series 2 annual service

How to fix annual startup and maintenance schedule: step by step

  1. Investigate any reported problems.
  2. Inspect and clean the air inlet box screen, and do not use solvents.
  3. Clean the base collector and condensate trap and refill with fresh water.
  4. Check for water, gas, flue and condensate leaks.
  5. Check water chemistry, inhibitor and antifreeze concentration.
  6. Check the boiler relief valve and expansion tank.
  7. Inspect the flue and air lines for condition and tightness.
  8. Inspect, clean and check spacing of the ignition electrode and flame sense rods.
  9. Check the high gas pressure switch, low gas pressure switch, low water cutoff, and operating and high limits.
  10. Run startup checkout and verify flame stability and flame signal.
  11. Clean the heat exchanger if flue temperature is more than 30 °F above return water temperature.
  12. Check blower speed settings.
  13. Owner daily: check boiler area, air openings and pressure/temperature gauge.
  14. Owner monthly: check vent piping, air piping, relief valve, condensate drain and automatic air vents.
  15. Owner periodically: test the low water cutoff using the test button.
  16. Owner every six months: check boiler piping for gas and water, and operate the relief valve.
  17. Owner at end of season: shut the boiler down unless it supplies domestic hot water.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 86. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.