Weil-McLain Boiler: Additional limits and low water protection
Additional limits and low water protection on a Weil-McLain boiler: The control provides high limit and low water protection. Some jurisdictions require external limits.
Applies to: All SlimFit boilers
How to fix additional limits and low water protection: step by step
- Check local codes to see if extra limit devices are needed.
- For low temperature circuits on a mixed system, wire external limits to the control P13 terminals.
- For manual reset, use series isolated contacts on P13 terminals 1 and 2.
- For automatic reset, use series isolated contacts on P13 terminals 3 and 4.
- Test the push-to-test low water cutoff on the supply manifold by removing the jacket. It resets manually through the control.
- Install a backflow check valve in the cold water supply where local codes require it.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit 550/750 Series 3 boiler manual, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.