Weil-McLain Boiler: Additional high temperature limit in ASME systems
Additional high temperature limit in ASME systems on a Weil-McLain boiler: ASME installations may need a manual reset high temperature limit in the supply piping between the boiler and its isolation valve. Its setting must stay below 240°F. The Unity CI control shuts the boiler down at 210°F, or lower if set lower.
Applies to: CGi Series 5 boilers with Unity CI control
How to fix additional high temperature limit in asme systems: step by step
- Where ASME applies, install a manual reset high temperature limit in supply piping between the boiler and isolation valve.
- Set the external limit below 240°F.
- Confirm the Unity CI operating limit (210°F or lower) is the boiler shutdown point.
- Check local codes for other requirements.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: CGi Series 5 gas-fired water boiler manual, p. 43. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.