Weil-McLain Boiler: Additional high temperature limit in ASME systems

Updated · by Aurora Star Tech Inc.

Additional high temperature limit in ASME systems on a Weil-McLain boiler: ASME installations may need a manual reset high temperature limit in the supply piping between the boiler and its isolation valve. Its setting must stay below 240°F. The Unity CI control shuts the boiler down at 210°F, or lower if set lower.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: CGi Series 5 boilers with Unity CI control

How to fix additional high temperature limit in asme systems: step by step

  1. Where ASME applies, install a manual reset high temperature limit in supply piping between the boiler and isolation valve.
  2. Set the external limit below 240°F.
  3. Confirm the Unity CI operating limit (210°F or lower) is the boiler shutdown point.
  4. Check local codes for other requirements.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: CGi Series 5 gas-fired water boiler manual, p. 43. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.