Weil-McLain Boiler: Add a DHW secondary connection for high-flow or high pressure-drop DHW
Add a DHW secondary connection for high-flow or high pressure-drop DHW on a Weil-McLain boiler: Use this layout when DHW circuit flow exceeds what the boiler allows, or when a coil-type DHW tank has high pressure drop. DHW water flows only through the secondary connection piping.
Applies to: SlimFit 1000-2000 Series 2
Common causes of add a dhw secondary connection for high-flow or high pressure-drop dhw
- DHW flow rate above boiler limits
- High pressure-drop coil-type DHW tank
How to fix add a dhw secondary connection for high-flow or high pressure-drop dhw: step by step
- Size the DHW secondary connector piping (Figure 17, item 23) for the full flow it must carry.
- Keep the DHW secondary connector tees no more than 8 pipe diameters apart.
- Install a system circulator sized for the required flow and head.
- Install a flow/check valve on the boiler outlet piping.
- Set DHW priority and space heating priority as shown in the priority setting table.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 Boiler Manual, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.