Weil-McLain Boiler: 0-10 VDC remote target input wiring and setup
0-10 VDC remote target input wiring and setup on a Weil-McLain boiler: Optional remote target. A 0-10 VDC signal on P15-5/6 (positive on terminal 6, common on terminal 5) adjusts the supply target temperature through the TARGET ADJUST setting. It replaces the outdoor sensor as the target modifier. The control does not control the target itself. A dry contact heat demand must still be wired to an input to start a call for heat.
Applies to: SF1000L/R, SF1500L/R, SF2000L/R
How to fix 0-10 vdc remote target input wiring and setup: step by step
- Wire the 0-10 VDC signal to P15 terminal 6 (positive) and terminal 5 (common).
- Assign the heat demand dry contact to an unused input and its pump or valve to the matching output.
- Assign a priority to that input in the Wizard or contractor menu.
- Use PRIORITY 1 for DHW if used, and PRIORITY 2 for space heating.
- Set TARGET ADJUST to 0-10V in the PRIORITY 2 menu.
- Set VOLTS FOR MAX and SUPPLY MAX for the highest target temperature.
- Set VOLTS FOR MIN and SUPPLY MIN for the lowest target temperature.
- Voltages between the two points give a proportional target between SUPPLY MIN and SUPPLY MAX.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 57. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.