Viessmann Water Heater: Temperature and pressure relief valve discharge line
Temperature and pressure relief valve discharge line on a Viessmann water heater: The T&P valve is supplied with the tank and must be installed to code. The discharge line must be safe for attendants and must not restrict flow.
Applies to: Vitocell 100-V CVWC T&P valve
How to fix temperature and pressure relief valve discharge line: step by step
- Install the T&P valve in the pipe connection point shown in the manual.
- Run the discharge line to a safe discharge point about 1 ft (305 mm) above the floor, close to a floor drain.
- Keep the discharge line as short as possible, pitch it downward from the valve, and end it plain, not threaded.
- Orient the discharge line so it does not scald people.
- Do not route the discharge line directly outdoors.
- Do not install any valve or restriction between the tank and the T&P valve, or between the valve and the discharge outlet.
- Have the owner operate the test lever at least once a year.
- Have the heating contractor re-inspect the T&P valve at least every three years.
If the unit shows an error code, look it up: Viessmann Water Heater codes
Models
Vitocell 100-V CVWC 53 USG (200 L)Vitocell 100-V CVWC 66 USG (250 L)Vitocell 100-V CVWC 79 USG (300 L)
Source: Vitocell 100-V CVWC installation, service and operating instructions, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.