Viessmann Water Heater: Heating system connections for solar with extra tank
Heating system connections for solar with extra tank on a Viessmann water heater: Recommended piping for a solar application with an additional tank. The DHW temperature must be limited to 140°F (60°C) with an anti-scald tempering valve. The valve does not fully remove scald risk, so a mixing tap is recommended.
Applies to: Vitocell 100-V CVWC with solar and boiler heating
How to fix heating system connections for solar with extra tank: step by step
- For boiler supply temperatures over 203°F (95°C), remove the plastic supply and return grommets (left-threaded).
- Pipe the supply line with an incline and install an air vent valve at the highest point.
- For boiler supply temperatures over 230°F (110°C), install a type-tested high limit safety cut-out, unless one is already installed. Use a dual thermostat (high limit thermostat and high limit safety cut-out).
- Close off test nipples that are not used for a probe or sensor.
- Order the tee with sensor well for solar return separately.
If the unit shows an error code, look it up: Viessmann Water Heater codes
Models
Vitocell 100-V CVWC 53 USG (200 L)Vitocell 100-V CVWC 66 USG (250 L)Vitocell 100-V CVWC 79 USG (300 L)
Source: Vitocell 100-V CVWC installation, service and operating instructions, p. 21. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.