Viessmann Mini-Split: Temperature sensor identification
Temperature sensor identification on a Viessmann mini-split: The unit uses five temperature sensors: room (T1), indoor coil (T2), outdoor coil (T3), outdoor ambient (T4) and compressor discharge (T5). Test each sensor with a tester after disconnecting it from the PCB.
Applies to: Indoor and outdoor temperature sensors
How to fix temperature sensor identification: step by step
- Disconnect the temperature sensor from the PCB.
- Measure the resistance of the sensor with a tester.
- Identify the sensor: T1 room, T2 indoor coil, T3 outdoor coil, T4 outdoor ambient, T5 compressor discharge.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Source: DLFSFBH Service Manual, p. 38. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.