Viessmann Mini-Split: Set static pressure or automatic airflow with the wired controller
Set static pressure or automatic airflow with the wired controller on a Viessmann mini-split: Use the wired controller (KSACN0701AAA) to pick a fan curve SP1 to SP4 or run automatic airflow (AF) for the duct system. Confirm the coil is dry first.
Applies to: Ducted indoor units, wired controller KSACN0701AAA
How to fix set static pressure or automatic airflow with the wired controller: step by step
- Run the unit 2 hours in FAN ONLY mode to dry the coil if it is wet.
- Check the power wiring and ducting are complete, dampers are set, and the filter is in place.
- If there is more than one inlet or outlet, balance the dampers so each matches design airflow. Run FAN ONLY and use AF to step airflow from H to L.
- Turn the indoor unit OFF with the wired controller.
- With the system off, press and hold COPY for about 4 seconds.
- Press + or - to scroll to SP or AF. Do not select the T1, T2, T2b, T3 or T4 thermistor sub-menus.
- For manual SP: select SP, press CONFIRM, pick SP1 to SP4, then power down the unit to lock the setting.
- For AF: select AF and press CONFIRM. The ON light flashes during the run. Wait 3 to 6 minutes for the run to finish and the unit to stop.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Source: Viessmann DLFSDAH & DLFLDAH Technical Data Manual, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.