Viessmann Mini-Split: Set external static pressure or run automatic airflow adjustment
Set external static pressure or run automatic airflow adjustment on a Viessmann mini-split: Setting the fan performance to match the ducts, using the wired controller.
Applies to: Ducted indoor units with wired controller KSACN0501AAA
How to fix set external static pressure or run automatic airflow adjustment: step by step
- Confirm the test run is on a dry coil; if not, run FAN ONLY for 2 hours to dry it.
- Check power wiring and duct work are finished, any closing dampers are open, and the filter is fitted in the return.
- Adjust dampers so each inlet and outlet matches its design airflow, with the unit in FAN ONLY.
- Use the airflow button on the remote to choose H or L, then turn the indoor unit OFF.
- With the system off, press and hold COPY for about 4 seconds.
- Press + or - to scroll to SP or AF, then press CONFIRM.
- For manual SP: pick SP1 to SP4 using the fan curves, then power down the unit to lock it in.
- For AF: press CONFIRM. ON flashes while the fan runs; the unit stops by itself after 3 to 6 minutes.
- If there is no charge to the ventilation paths after adjustment, reset the automatic airflow adjustment and contact the dealer if it persists.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Source: Vitocal IND-D technical data manual, p. 13. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.