Viessmann Mini-Split: Refrigerant line installation
Refrigerant line installation on a Viessmann mini-split: Lines are shipped with R410A charge on the outdoor unit. Buried lines need limits and a rise at the service valves.
Applies to: All 24K, 36K, 48K systems
How to fix refrigerant line installation: step by step
- Do not bury lines in the ground.
- If a line must be buried, keep the buried length to 36 in (914 mm) or less.
- Provide at least a 6 in (152 mm) vertical rise to the service valves to stop refrigerant migration.
- Insulate both lines with at least 1/2 in (12.7 mm) thick insulation.
- Use closed-cell insulation for long line runs.
- Isolate interconnecting tubing from the building structure so vibration and noise do not transfer.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Source: Viessmann Vitocal IND-C ductless technical data manual, p. 7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.