Viessmann Mini-Split: Maintain indoor unit clearances
Maintain indoor unit clearances on a Viessmann mini-split: Keep the required space around the indoor unit so return airflow and service access are not restricted.
Applies to: All DLFSHC indoor units
How to fix maintain indoor unit clearances: step by step
- Keep at least 5.9 in (15 cm) above the unit for return airflow.
- If space is tight, the top clearance can be reduced to 2 in (50 mm), but only if the left and right clearances are still met.
- Keep at least 4.75 in (12 cm) clearance on the sides.
- Reducing the top clearance may reduce unit performance.
- Check the 6 ft (1.8 m) dimension shown in the clearance figure against the job layout.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Models
DLFSHCH06XAKDLFSHCH09XAKDLFSHCH12XAJDLFSHCH12XAKDLFSHCH18XAKDLFSHCH24XAKDLFSHCH30XAKDLFSHCH36XAK
Source: DLFSHC installation instructions, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.