Viessmann Mini-Split: Indoor to outdoor wiring requirements
Indoor to outdoor wiring requirements on a Viessmann mini-split: Power and communication run as four conductors. Polarity matters, and BX cable is not recommended.
Applies to: DLFSCBH and DLFLCBH 24K, 36K, 48K
How to fix indoor to outdoor wiring requirements: step by step
- Size wire per NEC or CEC and local codes, using the MCA and MOCP values from the electrical data table.
- Use 14/3 stranded wire with ground, 600 V rated, between outdoor and indoor units.
- Two conductors carry line voltage, one is communication (S), and one is ground.
- Keep the wiring polarity correct between the indoor and outdoor units.
- In high EMF areas with communication problems, use 14/2 stranded shielded wire for L2 and S, and land the shield to ground at the outdoor unit only.
- Make every connection tight and keep wires clear of refrigerant tubing, the compressor and moving parts.
- Provide a disconnect within sight of and readily accessible from the air conditioner.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
More commissioning tips for mini-split
Source: Viessmann Vitocal IND-C ductless technical data manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.