Viessmann Mini-Split: Field wiring between outdoor and indoor units
Field wiring between outdoor and indoor units on a Viessmann mini-split: Power and communication wires run between the outdoor and indoor units. Wire size depends on the unit size. Wire must be sized to NEC/CEC and local codes using outdoor unit MCA and MOCP.
Applies to: Sizes 09 to 58
Common causes of field wiring between outdoor and indoor units
- Loose terminations can overheat or cause malfunction
- Wire touching refrigerant tubing, compressor or moving parts
How to fix field wiring between outdoor and indoor units: step by step
- Size all wires per NEC or CEC and local codes using outdoor MCA and MOCP.
- Sizes 09 to 24: run four conductors (two AC power, one communication, one ground) using 14/3 power and communication wire.
- If EMF interference occurs on sizes 09 to 24, use 14/2 stranded shielded wire in place of L2 and S, grounding the shield at the outdoor unit only.
- Sizes 36 to 58: run three power conductors (two AC power and one ground), 14/2 stranded with ground recommended.
- Sizes 36 to 58: run a separate shielded stranded copper communication wire, 600 V rated, 16 GA stranded control wire.
- Tighten every connection; check no wire touches refrigerant tubing, compressor or moving parts.
- Install a disconnect within sight and readily accessible from the system.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Source: Viessmann DLFSDAH & DLFLDAH Technical Data Manual, pp. 10 and 11. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.