Viessmann Mini-Split: Field wiring between indoor and outdoor unit
Field wiring between indoor and outdoor unit on a Viessmann mini-split: Power and communication run as four conductors. Two are line voltage, one is the communication (S) wire, and one is ground. The polarity matters. Do not use BX cable.
Applies to: DLFSFBH 12K ductless system field wiring
How to fix field wiring between indoor and outdoor unit: step by step
- Use 14/3 stranded wire with ground, rated 600 V, for the outdoor-to-indoor run.
- If there is high EMF interference and communication problems, you may use 14/2 stranded shielded wire in place of L2 and S. Land the shield to ground at the outdoor unit only.
- Size wire per NEC/CEC and local code, using the outdoor unit MCA and MOCP values.
- Make every connection firmly. Keep wires away from refrigerant tubing, the compressor and moving parts.
- Provide a disconnect within sight of and readily accessible from the unit.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
More other tips for mini-split
Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 4. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.