Viessmann Mini-Split: Evaporator low temperature protection (T2)

Updated · by Aurora Star Tech Inc.

Evaporator low temperature protection (T2) on a Viessmann mini-split: The compressor is limited or stopped when the evaporator pipe temperature (T2) is low.

Homeowner with a ductless mini-split problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Evaporator temperature sensor T2, DLFSFBH 12K

Common causes of evaporator low temperature protection (t2)

  • T2 below 32 °F (0 °C)
  • T2 between 32 and 39.2 °F (0 to 4 °C)

How to fix evaporator low temperature protection (t2): step by step

  1. If T2 is below 32 °F (0 °C), the compressor stops and restarts when T2 reaches 41 °F (5 °C).
  2. If T2 is 32 to 39.2 °F (0 to 4 °C), the compressor frequency is reduced to a lower level.
  3. If T2 is 39.2 to 44.6 °F (4 to 7 °C), the compressor holds its current frequency.
  4. If T2 is above 44.6 °F (7 °C), the compressor frequency is not limited.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Mini-Split codes

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 8. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.