Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Mini-Split: Evacuate and charge system with vacuum pump

Updated · by Aurora Star Tech Inc.

Evacuate and charge system with vacuum pump on a Viessmann mini-split: Evacuate all circuits at once through the low side master service valve charge port. Break vacuum with dry nitrogen only. Factory charge in the outdoor unit covers line length up to 25 ft (8 m). Note: all units except the 18,000 BTU model have a master suction and liquid line service valve.

Homeowner with a ductless mini-split problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: System evacuation and charging, all DLFSHC sizes

How to fix evacuate and charge system with vacuum pump: step by step

  1. Tighten the flare nuts (A, B, C, D, E) fully.
  2. Fully open all circuit service valves.
  3. Connect the manifold gauge charge hose to the charge port of the low side master service valve.
  4. Connect the other charge hose to the vacuum pump.
  5. Fully open the low side of the manifold gauge.
  6. Start the vacuum pump and evacuate using the triple evacuation method.
  7. When evacuation is complete, fully close the low side of the gauge manifold and stop the pump.
  8. Disconnect the charge hose from the low side service valve charge connection.
  9. Tighten the service valve caps securely.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Mini-Split codes

Models

DLFSHCH06XAKDLFSHCH09XAKDLFSHCH12XAJDLFSHCH12XAKDLFSHCH18XAKDLFSHCH24XAKDLFSHCH30XAKDLFSHCH36XAK

Source: DLFSHC service manual, p. 9. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency HVAC Service