Viessmann Mini-Split: Electrical parts removal, sizes 48K-58K
Electrical parts removal, sizes 48K-58K on a Viessmann mini-split: Steps to disconnect power and ground wires, remove the main control board and fan motor capacitors. Connections noted on the diagram: low and high pressure switch, T3 and T4, TP to indoor unit, and wires from the main board to the IPM module board.
Applies to: DLCLRC outdoor unit, sizes 48K and 58K (Models 48AAK, 58AAK)
How to fix electrical parts removal, sizes 48k-58k: step by step
- Remove the 2 screws to disconnect the power supply wires.
- Remove the 3 screws to disconnect the ground wires.
- Disconnect the wires connected to the main control board.
- Disconnect the wires between the main control board and the IPM module board.
- Remove the 4 screws and loosen the 6 hooks, then remove the main control board.
- Remove 1 screw per fan motor capacitor, then remove the capacitor.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Source: DLCLRC service manual, p. 47. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.