Viessmann Mini-Split: Communication line DC voltage check (indoor to outdoor)
Communication line DC voltage check (indoor to outdoor) on a Viessmann mini-split: Used with EL 01 to check the signal between the indoor and outdoor units.
Applies to: DLFSOAH 09XAK / 18XAK
How to fix communication line dc voltage check (indoor to outdoor): step by step
- Use a multimeter on DC volts.
- Measure between the 2 port (or S or L2) and the 3 port (or N or S) of the outdoor unit. Red probe on the 2 port (or S or L2), black probe on the 3 port (or N or S).
- With the unit running normally, the reading swings between positive and negative values.
- If the reading is always positive, suspect the outdoor unit.
- If the reading stays at a fixed value, suspect the indoor unit.
- Check the reactor by measuring its resistance without the capacitor connected; it should be close to 0 ohm. Replace it if not.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Source: DLFSOAH Service Manual, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.