Viessmann Mini-Split: Communication line DC voltage and reactor check

Updated · by Aurora Star Tech Inc.

Communication line DC voltage and reactor check on a Viessmann mini-split: Used with EL 01 to decide whether the indoor or outdoor side has failed.

Homeowner with a ductless mini-split problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Indoor and outdoor communication, EL 01

Common causes of communication line dc voltage and reactor check

  • Faulty outdoor PCB if the reading is always positive
  • Faulty indoor side if the reading is fixed
  • Faulty reactor if its resistance is not near zero

How to fix communication line dc voltage and reactor check: step by step

  1. Measure the DC voltage between the 2 port (or S or L2) and the 3 port (or N or S) of the outdoor unit. Red pin on 2 (or S or L2), black pin on 3 (or N or S).
  2. Normal operation: the voltage alternates between positive and negative.
  3. If the voltage is always positive, the outdoor unit has a fault.
  4. If the voltage stays at a fixed value, the indoor unit has a fault.
  5. Disconnect the reactor from the capacitor and measure its resistance. A good reactor reads close to zero ohms. Replace it if not.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Mini-Split codes

Source: DLFSFBH Service Manual, p. 17. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.