Viessmann Mini-Split: Communication line DC voltage and reactor check
Communication line DC voltage and reactor check on a Viessmann mini-split: Used with EL 01 to decide whether the indoor or outdoor side has failed.
Applies to: Indoor and outdoor communication, EL 01
Common causes of communication line dc voltage and reactor check
- Faulty outdoor PCB if the reading is always positive
- Faulty indoor side if the reading is fixed
- Faulty reactor if its resistance is not near zero
How to fix communication line dc voltage and reactor check: step by step
- Measure the DC voltage between the 2 port (or S or L2) and the 3 port (or N or S) of the outdoor unit. Red pin on 2 (or S or L2), black pin on 3 (or N or S).
- Normal operation: the voltage alternates between positive and negative.
- If the voltage is always positive, the outdoor unit has a fault.
- If the voltage stays at a fixed value, the indoor unit has a fault.
- Disconnect the reactor from the capacitor and measure its resistance. A good reactor reads close to zero ohms. Replace it if not.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Source: DLFSFBH Service Manual, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.