Viessmann Mini-Split: Buried refrigerant pipe limits
Buried refrigerant pipe limits on a Viessmann mini-split: Burying refrigerant pipe deeper or longer than allowed can let refrigerant migrate into the cold buried section during shutdown, causing slugging and possible compressor damage at start-up.
Applies to: Refrigerant piping routed underground
How to fix buried refrigerant pipe limits: step by step
- Do not bury more than 36 in. (914 mm) of refrigerant pipe.
- If any pipe is buried, provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
More commissioning tips for mini-split
Source: DLFSCBH and DLFLCBH installation instructions, p. 3. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.