Viessmann Heat Pump: Water connections and piping
Water connections and piping on a Viessmann heat pump: Support all piping on hangers so no load goes onto the unit. Flush the heating system before connecting, especially before tying the heat pump into an existing system. Ground loop connections use NPS straight thread and need gasketed fittings. Use an approved pipe sealant or Teflon tape on the other fittings. Do not exceed the listed pressures or temperatures, or the warranty is void.
Applies to: Vitocal 100-WA, all models
How to fix water connections and piping: step by step
- Flush the heating system thoroughly, especially before connecting to an existing system.
- Connect the ground loop return (A) and supply (B) using double O-ring fittings supplied in the field; remove the caps first.
- Connect the DHW tank supply (E) and tank return (F) using approved sealant or Teflon tape.
- Use two wrenches when tightening fittings onto the heat pump connectors: one holds the connector to stop twisting, the other tightens the fitting.
- Support all piping with hangers; do not support piping by the unit or its components.
- Install isolation valves so system components can be isolated.
- Make sure the condensate line (C) is connected.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
Source: vitocal_100-wa_ap1t_ios.pdf, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.