Viessmann Heat Pump: Verify refrigerant leak mitigation (GAS fault)
Verify refrigerant leak mitigation (GAS fault) on a Viessmann heat pump: When the A2L sensor detects leaked refrigerant, the compressor is shut off and the blower runs continuously. The display flashes GAS until power is cycled. Use this check to confirm the mitigation is working.
Applies to: Ducted installations using the blower for leak mitigation
Common causes of verify refrigerant leak mitigation (gas fault)
- A2L refrigerant leak sensor detected leaked refrigerant.
How to fix verify refrigerant leak mitigation (gas fault): step by step
- Confirm GAS fault is shown on the information display.
- On Screen 1, confirm LFL% is above 15%.
- Confirm compressor percentage is 0.
- Confirm fan % is above 10%.
- At the control board, confirm C1 and C2 outputs are not supplying 24VAC to the compressor start relay.
- At the start relay, confirm the 24VAC coil side and 230V load side are not energized.
- At the compressor molded plug, confirm there is no amp draw on the common, start or run wire.
- At the control board ECM terminal, confirm 12VDC ±0.5V between G and C.
- At the blower high voltage connector, confirm amp draw on T1 and T2 while the blower runs. Do not unplug the motor while it is running.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
Source: Vitocal 100-WA installation, service and operating instructions, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.