Viessmann Heat Pump: Strip heater fan enable (F-F) wiring
Strip heater fan enable (F-F) wiring on a Viessmann heat pump: The F-F pair is the fan enable relay coil and is how the heater proves air movement. The elements cannot energize on a heat call unless 24 VAC is also present across F-F. The relay only proves the blower was called, not the airflow.
Applies to: Optional electric strip heat accessory
Common causes of strip heater fan enable (f-f) wiring
- No 24 VAC across F-F when the blower is called, so elements will not energize
How to fix strip heater fan enable (f-f) wiring: step by step
- Land one F on the thermostat G terminal at the control board; the G terminal carries 24 VAC only while the blower is called.
- Share the G screw with the thermostat G lead, since there is no spare G terminal.
- Land the second F on control common, using a jumper from terminal C at the heater.
- Run the third conductor in the same cable as the AUX pair.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
Source: Vitocal 100-WA installation, service and operating instructions, p. 37. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.