Viessmann Heat Pump: Strip heat start-up and commissioning checks
Strip heat start-up and commissioning checks on a Viessmann heat pump: Verify the installation before leaving the site.
Applies to: Optional electric strip heat accessory
How to fix strip heat start-up and commissioning checks: step by step
- Confirm the heater branch circuit is separate from the heat pump supply and fused per the heater data plate.
- Confirm the heater is side mounted and at the required distances.
- Verify AUX polarity: B to heater terminal 1, W to heater terminal C.
- Verify fan interlock wiring and confirm 24 VAC across F-F whenever the blower is called.
- Run the blower on high speed and verify airflow meets or exceeds the heater minimum.
- Verify the inlet air temperature at the heater does not exceed 100°F (38°C).
- Put the thermostat in emergency/auxiliary heat and verify the AUX output energizes and the contactor pulls in.
- Observe at least one complete heating cycle to confirm normal heater and safety limit operation.
- Record the heater model number, kW rating and job number in the maintenance record.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
Source: Vitocal 100-WA installation, service and operating instructions, p. 38. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.