Viessmann Heat Pump: Service checks for installations using flammable refrigerant
Service checks for installations using flammable refrigerant on a Viessmann heat pump: Checks to carry out on installations with flammable refrigerant.
Applies to: Vitocal 100-WA installations with R-454B
How to fix service checks for installations using flammable refrigerant: step by step
- Confirm the actual refrigerant charge suits the size of the room where refrigerant-containing parts are installed.
- Confirm ventilation machinery and outlets work properly and are not blocked.
- If an indirect refrigerating circuit is used, check the secondary circuit for refrigerant.
- Confirm equipment markings are still visible and legible. Correct any illegible markings and signs.
- Confirm refrigerant pipes and components are not exposed to substances that could corrode them, unless they are corrosion-resistant or protected.
- Check that cabling will not be exposed to wear, corrosion, excessive pressure, vibration, sharp edges or other adverse conditions, including ageing and vibration from compressors or fans.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 57. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.