Viessmann Heat Pump: Refrigerant line insulation and buried pipe limits
Refrigerant line insulation and buried pipe limits on a Viessmann heat pump: Insulate the two refrigerant lines separately. Do not bury more than 36 in. (914 mm) of refrigerant pipe. If any section is buried, it must rise at least 6 in. (152 mm) to the outdoor unit valve connections. Too much buried pipe lets refrigerant migrate to the cold section during shutdown, which can cause slugging and compressor damage at start-up.
Applies to: DLFSHCH refrigerant piping
How to fix refrigerant line insulation and buried pipe limits: step by step
- Insulate each refrigerant line separately.
- Keep total buried refrigerant pipe to 36 in. (914 mm) or less.
- If pipe is buried, provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
More commissioning tips for heat pump
Source: Vitocal IND-H DLFSHC service manual, p. 2 and p. 7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.