Viessmann Heat Pump: Refrigerant leak checks on flammable refrigerant systems
Refrigerant leak checks on flammable refrigerant systems on a Viessmann heat pump: Do not use any open flame to look for leaks. Use detectors that suit the refrigerant and are not ignition sources.
Applies to: Vitocal 100-AW AM2V outdoor unit refrigerant circuit
How to fix refrigerant leak checks on flammable refrigerant systems: step by step
- Do not use a halide torch or any naked-flame detector.
- Use an electronic leak detector rated for the refrigerant and calibrated in a refrigerant-free area. Note that its sensitivity may be lower for flammable refrigerants.
- Set leak detection to 25% of the lower flammable limit at most.
- Use leak detection fluid only if it contains no chlorine.
- Remove or put out all open flames if a leak is suspected.
- If the leak needs brazing, recover all refrigerant or isolate the leaking section with shut-off valves first.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
0200280340430510780340043AM2V 020028AM2V 034043AM2V 051078
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.