Viessmann Heat Pump: Pressure relief valve and discharge piping (indoor unit)
Pressure relief valve and discharge piping (indoor unit) on a Viessmann heat pump: Install the factory-supplied approved 30 PSI relief valve on the supply-from-outdoor-unit connection, then pipe the discharge to a floor drain. Keep the discharge clear of anyone standing nearby.
Applies to: Vitocal 100-AW AM2V indoor unit
How to fix pressure relief valve and discharge piping (indoor unit): step by step
- Use the supplied fittings to fit the 30 PSI relief valve on the supply-from-outdoor-unit connection (see piping connections on p. 22).
- Use only the approved factory-supplied relief valve.
- Do not fit any isolation valve between the heat pump and the relief valve.
- Thread-free end on the discharge pipe; do not reduce the discharge pipe diameter.
- Run the discharge pipe to a floor drain and end it about 6 in. (150 mm) above the drain.
- Orient the discharge so it cannot scald people.
- Do not put a shutoff valve in the discharge pipe.
- Never pipe the discharge to the outdoors.
- Make sure supply and return lines have no restrictive piping where air can get trapped; purge air through the air vents in the supply.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Source: Vitocal 100-AW AM2V installation manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.