Viessmann Heat Pump: Preparing the refrigerant circuit for service
Preparing the refrigerant circuit for service on a Viessmann heat pump: Steps to complete before opening or working on the refrigerant circuit. The unit uses R-454B, which is heavier than air and forms explosive mixtures.
Applies to: Vitocal 100-WA
How to fix preparing the refrigerant circuit for service: step by step
- Check the refrigerant circuit for leaks.
- Make sure the room is very well ventilated, especially at floor level, and keep it that way for the whole job.
- Secure the work area and warn maintenance staff and people nearby about the work.
- Remove all flammable and movable materials and ignition sources from the area around the heat pump.
- Check the surrounding air for escaping refrigerant before, during and after the work, using an explosion-proof detector rated for R-454B that cannot create sparks.
- Keep a CO2 or dry powder extinguisher at hand when draining refrigerant, topping up refrigerant, or brazing or welding.
- Post no-smoking signs.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
Source: vitocal_100-wa_ap1t_ios.pdf, p. 4. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.