Viessmann Heat Pump: Outdoor DC fan motor winding check
Outdoor DC fan motor winding check on a Viessmann heat pump: Checks whether the fault is in the motor or in the outdoor PCB.
Applies to: Vitocal IND-A DLFUAA air handler, models 18XAK to 60XAK
How to fix outdoor dc fan motor winding check: step by step
- Shut off the power.
- Release the UVW connector.
- Measure resistance U-V, U-W and V-W.
- If the three values are not equal, replace the fan motor.
- If the three values are equal, replace the outdoor PCB.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Source: Viessmann Vitocal IND-A DLFUAA service manual, p. 21. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.