Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Heat Pump: Outdoor DC fan motor test

Updated · by Aurora Star Tech Inc.

Outdoor DC fan motor test on a Viessmann heat pump: Test the outdoor DC fan motor windings, feedback signal and rotation voltages.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: DLFSHC outdoor unit DC fan motor

How to fix outdoor dc fan motor test: step by step

  1. Release the UVW connector. Measure resistance between U-V, U-W and V-W. If the three values are not equal, replace the fan motor.
  2. If they are equal, power on the unit. When it is in standby, measure voltage between pin 4 and pin 5 of the feedback connector. If it is not 5 V, replace the PCB.
  3. Rotate the fan by hand. Measure voltage from pin 1 to pin 5, pin 2 to pin 5 and pin 3 to pin 5. If any reading does not fluctuate in positive voltage, replace the fan motor.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Heat Pump codes

Source: Viessmann Vitocal IND-H DLFSHC service manual, p. 22. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency HVAC Service

647-657-2977