Viessmann Heat Pump: Open loop well water requirements
Open loop well water requirements on a Viessmann heat pump: Use only a well of adequate capacity with good water quality. Do not pump pond or lake water through the unit. If groundwater may drop below 50°F (10°C) in heating season, calculate a higher flow rate. Install an 18-20 mesh strainer with isolation valves, and keep it accessible for cleaning. Discharge water to a well, creek, pond or other approved outlet, never directly to a sprinkler, and keep the line from freezing. Use 2-3 GPM/ton (7.5-11.5 LPM/3.5 kW) for open loops. Do not use PVC or CPVC on loop connections.
Applies to: Open loop systems
Common causes of open loop well water requirements
- Groundwater below 50°F during heating season
- Debris restricting the strainer
- Discharge restricted or connected to sprinkler
How to fix open loop well water requirements: step by step
- Confirm the well capacity and water quality.
- Install an 18-20 mesh strainer with isolation valves.
- Route discharge to an approved outlet without restrictions and protect it from freezing.
- Set water flow at 2-3 GPM/ton.
- Clean or upsize the strainer if debris restricts flow.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
Source: Vitocal 100-WA technical data manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.