Viessmann Heat Pump: Open loop well water piping and strainer
Open loop well water piping and strainer on a Viessmann heat pump: Open loop installs need a well of adequate capacity and good water quality. Do not use pond or lake water directly through the unit. PVC or CPVC may only be used for condensate lines, never on ground loop connections.
Applies to: Open loop systems
How to fix open loop well water piping and strainer: step by step
- Install a 18-20 mesh strainer in an easy-to-service location, with isolation valves so the system can be isolated for cleaning.
- Replace an undersized strainer with a larger 18-20 mesh unit if the well carries heavy debris.
- Route discharge water to an open discharge well, creek, pond or other point of use, with no restrictions and no leaks.
- Do not connect discharge directly to a sprinkler.
- Protect discharge tubing from freezing.
- Check local code requirements for discharge water.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
Source: Vitocal 100-WA technical data manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.