Viessmann Heat Pump: Open loop water source requirements
Open loop water source requirements on a Viessmann heat pump: Only a well or retention pond with enough capacity and good water quality is acceptable. Pond or lake water must not be pumped directly through the units.
Applies to: Open loop systems
How to fix open loop water source requirements: step by step
- Install an 18-20 mesh strainer in an easy-to-reach location.
- Provide isolation valves so the strainer can be cleaned.
- Replace an undersized well strainer with a larger 18-20 mesh unit if debris restricts it quickly.
- Route discharge water to a well, creek, pond or other use without restriction.
- Do not connect discharge directly to a sprinkler.
- Make sure discharge tubing cannot freeze.
- Water flow is controlled by a modulating water valve or an ON/OFF two position valve.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
More commissioning tips for heat pump
Source: Vitocal 100-WA installation, service and operating instructions, p. 42. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.