Viessmann Heat Pump: Nuisance tripping of the automatic limit (strip heater)
Nuisance tripping of the automatic limit (strip heater) on a Viessmann heat pump: Most nuisance trips come from low airflow, poor heater placement, or high incoming air temperature.
Applies to: Optional electric strip heat accessory
Common causes of nuisance tripping of the automatic limit (strip heater)
- Insufficient airflow across the heater
- Heater located too close to a fan, damper, elbow, turn or transition
- Inlet air temperature too high (110°F (43°C) or higher causes problems)
How to fix nuisance tripping of the automatic limit (strip heater): step by step
- Check airflow meets the heater minimum at high speed.
- Check heater placement against the required distances.
- Check the inlet air temperature at the heater is below 100°F (38°C).
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
Source: Vitocal 100-WA installation, service and operating instructions, p. 38. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.