Viessmann Heat Pump: IPM continuity check
IPM continuity check on a Viessmann heat pump: Procedure to check the IPM module continuity on the outdoor unit when an IPM-related fault (PC00) is present.
Applies to: Outdoor IPM module, PC00 fault
How to fix ipm continuity check: step by step
- Turn off the outdoor unit and disconnect the power supply.
- Discharge the electrolytic capacitors and make sure all stored energy is gone.
- Disassemble the outdoor PCB or the IPM board.
- Measure resistance between P and U, V, W, N, and between U, V, W and N, using the diode-style reference in Fig. 21.
- Compare readings with the reference table; replace the IPM board or outdoor PCB if they do not match.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Source: DLFSHC Service Manual, p. 28. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.