Viessmann Heat Pump: Install the pressure relief valve and discharge pipe
Install the pressure relief valve and discharge pipe on a Viessmann heat pump: Use the factory supplied pressure relief valve. Discharge must be piped safely to a floor drain, never outdoors.
Applies to: Indoor unit safety valve
How to fix install the pressure relief valve and discharge pipe: step by step
- Fit the supplied pressure relief valve on the Supply from Outdoor Unit connection using the supplied fittings.
- Do not install any isolation valve between the heat pump and the pressure relief valve.
- Run the discharge pipe to a floor drain and end it about 6 in. (150 mm) above the drain.
- Keep the discharge pipe end unthreaded, do not reduce its diameter, and do not install a shutoff valve in it.
- Do not pipe the discharge to the outdoors.
- Position the discharge so it cannot scald people nearby.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Source: Viessmann Vitocal 100-AW AM2V installation manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.